MDAT TXs

MDAT FRAME TRANSMITTERS Status as of: 10/18/07 
MDAT Frame Parameter Type Code Transmitter Device Name Data Source Format Full Scale LSB Value of 16 Bit Word Transmitter
Type
Unique PALs Composite Delay from $07 at RC Delay on Module from $07 Current 166 Module Location Diagnostic Receiver Name Notes
Time of Day LSW $3 G:MDAT03 CAMAC Data from BSTR Front End Bit Protocol Not Applicable Not Applicable C166
V13.2
16618L.DAT 16652I.DAT 160 us 156 us BSTR $B1 N22 N/A Configured to Always Come Up in CAMAC Mode. 
Time of Day MSW $4 G:MDAT04 CAMAC Data from BSTR Front End Bit Protocol Not Applicable Not Applicable C166
V13.2
16618L.DAT 16652I.DAT 170 us 166 us BSTR $B1 N23 N/A Configured to Always Come Up in CAMAC Mode. 
Tevatron Programmed I $10 T:MDAT10 TECAR Unsigned Positive Integer 5000 Amps 76.29 mA C166
V1.0
16618A.DAT 16652A.DAT 10 us 1 us TEV $A6 N17 T:MCRT10
Tevatron Programmed I Dot $11 T:MDAT11 TECAR Signed 2's Complement 439.453125 A/Sec 13.41mA/sec C166
V2.0
16618B.DAT 16652A.DAT 20 us 10.8 us TEV $A6 N18 T:MCRT11
Tevatron State $12 T:MDAT12 CAMAC Data from PA1028 Sequencer Bit Protocol Not Applicable Not Applicable C166
V13.1
16618L.DAT 16652I.DAT 220 us 217us BSTR $B1 N16 T:MCRT12 Configured to Always Come Up in CAMAC Mode. Used to be at SWYD $04 N9.
Tevatron Low Beta Squeeze Sequence # $13 T:MDAT13 CAMAC Data from PA C49 via CAMAC 467 Unsigned Positive Integer Not Applicable Not Applicable c166
V14.0
16618K.DAT 16652H.DAT 230 us 227 us BSTR $B2N5 T:MCRT13
Tevatron Measured I $20 T:MDAT20 TECAR (Pass Through of T:IRING) Unsigned Positive Integer 5000 Amps 76.29 mA C166
V3.0
16618C.DAT 16652A.DAT 30 us 20.3 us TEV $A6 N19 T:MCRT20 TECAR is Not the Actual Data Source.
Tevatron Measured I Dot  $21 T:MDAT21 TECAR Signed 2's Complement 439.453125 A/Sec 13.41 mA/sec C166
v4.0
16618D.DAT 16652A.DAT 40 us 31 us TEV $A6 N20 T:MCRT21 TECAR is Not the Actual Data Source. No Device Name for Actual Source.
Main Injector Programmed P $30 I:MDAT30 MECAR Unsigned Positive Integer 170 GeV 2.59x10-3 GeV MECAR
MDAT
CARD
mdatdsp4.ttf 50 us 45 us MECAR VME front end at MI60N slot 14 I:MCRT30 Test MECAR 166 was at MR $A2 N16. Was Ver 6.0, 16618I.DAT, 16652D.DAT
Main Injector Programmed P Dot $31 I:MDAT31 MECAR Signed 2's Complement 410 GeV/Sec 1.25x10-2 GeV/Sec MECAR
MDAT
CARD
mdatdsp4.ttf 60 us 55 us MECAR VME front end at MI60N slot 14 I:MCRT31 Test MECAR 166 was at MR $A2 N17. Was Ver. 7.0. 16618I.DAT, 16652D.DAT
Main Injector Measured I $40 I:MDAT40 MECAR (Pass Through of M:MIBEND) Unsigned Positive Integer 10000 Amps 152.59 mA MECAR
MDAT
CARD
mdatdsp4.ttf 70 us 64 us MECAR VME front end at MI60N slot 14 I:MCRT40 Test MECAR 166 was at MR $A2 N18. Source Used to be M:IB. Was Ver. 5.0. 16618I.DAT, 16652D.DAT
Main Injector Measured I Dot $41 I:MDAT41 MECAR (Pass Through of M:MDIBND) Signed 2's Complement 25000 A/Sec 762.96 mA/sec MECAR
MDAT
CARD
mdatdsp4.ttf 80 us 75 us MECAR VME front end at MI60N slot 14 I:MCRT41 Test MECAR 166 was at MR $A2 N19. Was Ver. 8.0. 16618I.DAT, 16652D.DAT
Tevatron Fixed-Target Intensity $50 T:MDAT50 T:IBEAMB Unsigned Positive Integer 5.36E+13 8.18E+08 C166
V11.1
16618H.DAT 16652E.DAT 90 us 76 us MI $F1 N2 T:MCRT50 Moved to Pick Up New Data Source. 166 was at BSTR $B1 N17.
Tevatron Colliding Physics Intensity/Low FT Intensity $51 T:MDAT51 T:IBEAM Unsigned Positive Integer 1.00E+13 1.53E+08 C166
V12.0
16618H.DAT 16652A.DAT 100 us 85 us MI $F1 N3 T:MCRT51 Transmits continuously at the request of Peter Lucas for QXR
Tevatron Time at 150 GeV $52 T:MDAT52 C:REMVB2 Unsigned Positive Integer 327,670 sec 10 sec C166
V13.0
16618J.DAT 16652G.DAT 110 us 106 us BSTR $B1 N18 T:MCRT52
Tevatron RF Anode Program $53 T:MDAT53 T:APG Unsigned Positive Integer 10 Volts 152.5925 mV C166
V14.0
16618K.DAT 16652H.DAT 120 us 103 us TRF $81 N5 T:MCRT53 Req'd per Reid. (3/17/99)
Main Injector Programmed P Prime - MSW - Exponent and Partial Fraction $54 I:MDAT54 MECAR IEEE Floating Point

MECAR
MDAT
CARD
mdatdsp4.ttf 130 us 125 us MECAR VME front end at MI60N slot 14 N/A Test MECAR 166 was at MR $A2 N22. Was Ver. 15.0. 16618I.DAT, 16652D.DAT
Main Injector Programmed P Prime - LSW - Remainder of Fraction $55 I:MDAT55 MECAR IEEE Floating Point

MECAR
MDAT
CARD
mdatdsp4.ttf 140 us 135 us MECAR VME front end at MI60N slot 14 N/A Test MECAR 166 was at MR $A2 N23. Was Ver. 16.0. 16618I.DAT, 16652D.DAT
Main Injector Cycle ID $56 I:MDAT56 TLG Bit Protocol Not Applicable Not Applicable TLG new_tlg.pof 180us 179 us TLG I:MCRT56 MI Machine Cycle ID for MILLRF
Main Injector Booster Batch Count $57 I:MDAT57 TLG Bit Protocol Not Applicable Not Applicable TLG new_tlg.pof 290us 291 us TLG   Number of Booster batches in MI Cycle 
Main Injector Fixed Target Intensity $60 I:MDAT60  I:IBEAMB Unsigned Positive Integer 9.70E+13 1.48E+09 C166
V9.0
16618I.DAT 16652D.DAT 200 us 157 us MI $32 N14 I:MCRT60 MI FT Ints. Used to be at TEV $A1 N19.
Main Injector CP/Low Fixed Target Intensity $61 I:MDAT61 I:IBEAMM Unsigned Positive Integer 2.66E+13 4.06E+08 C166
V9.0
16618I.DAT 16652D.DAT 210 us 167 us MI $32 N15 I:MCRT61 MI DCCT Mid Range Intensity
Main Injector Quad Difference Current $62 I:MDAT62 MECAR Signed Integer 120 Amps 3.6621 mA
mdatdsp4.ttf 150us 135 us MECAR VME front end at MI60N slot 14 I:MCRT62 Req'd per Krafczyk (3-21-00)
Tevatron FBI Proton Sum $70 T:MDAT70 Tev FBI Unsigned Positive Integer 1.00E+13 1.53E+08 8 Frame Xmitter ipmdat8.pof 240 us 226 us F0 CR C:MCRT70
Tevatron FBI Pbar Sum $71 T:MDAT71 Tev FBI Unsigned Positive Integer 1.00E+13 1.53E+08 8 Frame Xmitter ipmdat8.pof 250 us 236 us F0 CR C:MCRT71
Tevatron Intensity $72 T:MDAT72 T:BEAM Unsigned Positive Integer 5.36E+13 8.18E+08 8 Frame Xmitter ipmdat8.pof 260 us 246 us Tev DCCT front end F0CR C:MCRT72
Main Injector Intensity $73 I:MDAT73 I:BEAM Unsigned Positive Integer 9.70E+13 1.48E+09 8 Frame Xmitter ipmdat8.pof 270 us 230 us MI DCCT front end MI30 I:MCRT73
Filtered MI Intensity for QXR $73 I:MDAT74 I:BEAM Unsigned Positive Integer 9.70E+13 1.48E+09 8 Frame Xmitter ipmdat8.pof 280 us 240 us MI DCCT front end MI30 I:MCRT74
RR Start of Cold Beam $80 R:MDAT80 R:FPOS5 Bit Protocol 37632 RFC 1 RFC 8 Frame Xmitter ipmdat8.pof 300us 287 us MI60CR R:6CRT80 RR "A" position
RR End of Cold Beam $81 R:MDAT81 R:FPOS7 Bit Protocol 37632 RFC 1 RFC 8 Frame Xmitter ipmdat8.pof 310us 297 us MI60CR R:6CRT81 RR End of Cold Beam
RR Start of Stack Beam $82 R:MDAT82 R:FPOS3 Bit Protocol 37632 RFC 1 RFC 8 Frame Xmitter ipmdat8.pof 320us 307 us MI60CR R:6CRT82 RR Start of Stack Beam
RR End of Stack Beam $83 R:MDAT83 R:FPOS4 Bit Protocol 37632 RFC 1 RFC 8 Frame Xmitter ipmdat8.pof 330us 317 us MI60CR R:6CRT83 RR End of Stack Beam
RR Start of Transfer Beam $84 R:MDAT84 R:FPOS0 Bit Protocol 37632 RFC 1 RFC 8 Frame Xmitter ipmdat8.pof 340us 327 us MI60CR R:6CRT84 RR Start of Transfer Beam
RR End of Transfer Beam $85 R:MDAT85 R:FPOS1 Bit Protocol 37632 RFC 1 RFC 8 Frame Xmitter ipmdat8.pof 350us 337 us MI60CR R:6CRT85 RR End of Transfer Beam
Recycler Ring Cycle ID $86 R:MDAT86 TLG Bit Protocol Not Applicable Not Applicable 8 Frame Xmitter ipmdat8.pof 360us 361 us TLG R:6CRT86
 
Last Updated on 10/18/2007
By vogel
Email: vogel@fnal.gov